| Current rating | 7 amps stated as ampacity | FAA AC 43.13-1B Table 11-9, continuous duty in bundles, 105 C conductor rating; 70 C ambient, 33 or more wires in the bundle, no more than 20 percent of harness capacity used, 60,000 ft altitude | spec | raanz.org.nz 2026-11-08“16 7 11 14 4.81 2,426” |
|---|
| 11 amps stated as ampacity | FAA AC 43.13-1B Table 11-9, continuous duty in bundles, 150 C conductor rating; 70 C ambient, 33 or more wires in the bundle, no more than 20 percent of harness capacity used, 60,000 ft altitude | spec | raanz.org.nz 2026-11-08“16 7 11 14 4.81 2,426” |
| 14 amps stated as ampacity | FAA AC 43.13-1B Table 11-9, continuous duty in bundles, 200 C conductor rating; 70 C ambient, 33 or more wires in the bundle, no more than 20 percent of harness capacity used, 60,000 ft altitude | spec | raanz.org.nz 2026-11-08“16 7 11 14 4.81 2,426” |
| 6.5 A stated as ampacity | NASA EEE-INST-002 Table 4A derated current, bundled wire or multi-conductor cable; ambient 70 C or less, hard vacuum 1E-6 torr, 200 C rated wire such as PTFE; use 80 percent for 150 C wire and 70 percent for 135 C wire | spec | nepp.nasa.gov 2026-11-08“16 13.0 6.5” |
| 13.0 A stated as ampacity | NASA EEE-INST-002 Table 4A derated current, single wire; ambient 70 C or less, hard vacuum 1E-6 torr, 200 C rated wire such as PTFE; use 80 percent for 150 C wire and 70 percent for 135 C wire | spec | nepp.nasa.gov 2026-11-08“16 13.0 6.5” |
| 22 A stated as ampacity | PowerStream guideline, maximum amps for chassis wiring, meant for wiring in air and not in a bundle; the site calls it a rule of thumb | claim | powerstream.com 2026-11-09“16 0.0508 1.29032 1.31 4.016 13.17248 22 3.7” |
| 3.7 A stated as ampacity | PowerStream guideline, maximum amps for power transmission, uses 700 circular mils per amp, which the site calls very conservative | claim | powerstream.com 2026-11-09“16 0.0508 1.29032 1.31 4.016 13.17248 22 3.7” |
| 12 A stated as ampacity | Wikipedia AWG table, 60 C insulation column; enclosed wire at 30 C ambient, or single unbundled wires in equipment for 16 AWG and thinner | claim | en.wikipedia.org 2026-11-09“16 0.0508 1.291 19.7 7.75 2.58 1.31 13.17 4.016 12 16 18” |
| 16 A stated as ampacity | Wikipedia AWG table, 75 C insulation column; enclosed wire at 30 C ambient, or single unbundled wires in equipment for 16 AWG and thinner | claim | en.wikipedia.org 2026-11-09“16 0.0508 1.291 19.7 7.75 2.58 1.31 13.17 4.016 12 16 18” |
| 18 A stated as ampacity | Wikipedia AWG table, 90 C insulation column; enclosed wire at 30 C ambient, or single unbundled wires in equipment for 16 AWG and thinner | claim | en.wikipedia.org 2026-11-09“16 0.0508 1.291 19.7 7.75 2.58 1.31 13.17 4.016 12 16 18” |
| Conductor area | 2426 circ.mils = 1.229 mm² | FAA AC 43.13-1B Table 11-9, nominal conductor area | spec | raanz.org.nz 2026-11-08“16 7 11 14 4.81 2,426” |
|---|
| 2580 circular mils = 1.307 mm² | NIST Handbook 100 Table 5, standard annealed copper, solid round AWG size; a stranded wire's area differs | spec | nvlpubs.nist.gov 2026-11-09“16 50.8 2580 .002 03 4.02” |
| 1.31 mm2 | Wikipedia AWG table, solid round conductor | claim | en.wikipedia.org 2026-11-09“16 0.0508 1.291 19.7 7.75 2.58 1.31 13.17 4.016 12 16 18” |
| Resistance per length | 4.81 ohms/1000ft | FAA AC 43.13-1B Table 11-9, maximum at 20 C, tin plated conductor | spec | raanz.org.nz 2026-11-08“16 7 11 14 4.81 2,426” |
|---|
| 4.02 ohms per 1,000 feet | NIST Handbook 100 Table 5, standard annealed copper at 20 C, solid round AWG size | spec | nvlpubs.nist.gov 2026-11-09“16 50.8 2580 .002 03 4.02” |
| 13.17 mOhm/m | Wikipedia AWG table, solid copper wire at 68 F (20 C), computed based on 100% IACS conductivityReview note: Capture never says annealed; note [7] gives solid copper at 68 F (20 C) and 100% IACS, so the temperature condition is lost. | claim | en.wikipedia.org 2026-11-09“16 0.0508 1.291 19.7 7.75 2.58 1.31 13.17 4.016 12 16 18” |