| Current rating | 6 amps stated as ampacity | FAA AC 43.13-1B Table 11-9, continuous duty in bundles, 105 C conductor rating; 70 C ambient, 33 or more wires in the bundle, no more than 20 percent of harness capacity used, 60,000 ft altitude | spec | raanz.org.nz 2026-11-08“18 6 9 12 6.23 1,900” |
|---|
| 9 amps stated as ampacity | FAA AC 43.13-1B Table 11-9, continuous duty in bundles, 150 C conductor rating; 70 C ambient, 33 or more wires in the bundle, no more than 20 percent of harness capacity used, 60,000 ft altitude | spec | raanz.org.nz 2026-11-08“18 6 9 12 6.23 1,900” |
| 12 amps stated as ampacity | FAA AC 43.13-1B Table 11-9, continuous duty in bundles, 200 C conductor rating; 70 C ambient, 33 or more wires in the bundle, no more than 20 percent of harness capacity used, 60,000 ft altitude | spec | raanz.org.nz 2026-11-08“18 6 9 12 6.23 1,900” |
| 5.0 A stated as ampacity | NASA EEE-INST-002 Table 4A derated current, bundled wire or multi-conductor cable; ambient 70 C or less, hard vacuum 1E-6 torr, 200 C rated wire such as PTFE; use 80 percent for 150 C wire and 70 percent for 135 C wire | spec | nepp.nasa.gov 2026-11-08“18 9.2 5.0” |
| 9.2 A stated as ampacity | NASA EEE-INST-002 Table 4A derated current, single wire; ambient 70 C or less, hard vacuum 1E-6 torr, 200 C rated wire such as PTFE; use 80 percent for 150 C wire and 70 percent for 135 C wire | spec | nepp.nasa.gov 2026-11-08“18 9.2 5.0” |
| 16 A stated as ampacity | PowerStream guideline, maximum amps for chassis wiring, meant for wiring in air and not in a bundle; the site calls it a rule of thumb | claim | powerstream.com 2026-11-09“18 0.0403 1.02362 0.823 6.385 20.9428 16 2.3” |
| 2.3 A stated as ampacity | PowerStream guideline, maximum amps for power transmission, uses 700 circular mils per amp, which the site calls very conservative | claim | powerstream.com 2026-11-09“18 0.0403 1.02362 0.823 6.385 20.9428 16 2.3” |
| 10 A stated as ampacity | Wikipedia AWG table, 60 C insulation column; enclosed wire at 30 C ambient, or single unbundled wires in equipment for 16 AWG and thinner | claim | en.wikipedia.org 2026-11-09“18 0.0403 1.024 24.8 9.77 1.62 0.823 20.95 6.385 10 14 16” |
| 14 A stated as ampacity | Wikipedia AWG table, 75 C insulation column; enclosed wire at 30 C ambient, or single unbundled wires in equipment for 16 AWG and thinner | claim | en.wikipedia.org 2026-11-09“18 0.0403 1.024 24.8 9.77 1.62 0.823 20.95 6.385 10 14 16” |
| 16 A stated as ampacity | Wikipedia AWG table, 90 C insulation column; enclosed wire at 30 C ambient, or single unbundled wires in equipment for 16 AWG and thinner | claim | en.wikipedia.org 2026-11-09“18 0.0403 1.024 24.8 9.77 1.62 0.823 20.95 6.385 10 14 16” |
| Conductor area | 1900 circ.mils = 0.9627 mm² | FAA AC 43.13-1B Table 11-9, nominal conductor area | spec | raanz.org.nz 2026-11-08“18 6 9 12 6.23 1,900” |
|---|
| 1620 circular mils = 0.8209 mm² | NIST Handbook 100 Table 5, standard annealed copper, solid round AWG size; a stranded wire's area differs | spec | nvlpubs.nist.gov 2026-11-09“18 40.3 1620 .001 28 6.39” |
| 0.823 mm2 | Wikipedia AWG table, solid round conductor | claim | en.wikipedia.org 2026-11-09“18 0.0403 1.024 24.8 9.77 1.62 0.823 20.95 6.385 10 14 16” |
| Resistance per length | 6.23 ohms/1000ft | FAA AC 43.13-1B Table 11-9, maximum at 20 C, tin plated conductor | spec | raanz.org.nz 2026-11-08“18 6 9 12 6.23 1,900” |
|---|
| 6.39 ohms per 1,000 feet | NIST Handbook 100 Table 5, standard annealed copper at 20 C, solid round AWG size | spec | nvlpubs.nist.gov 2026-11-09“18 40.3 1620 .001 28 6.39” |
| 20.95 mOhm/m | Wikipedia AWG table, solid copper wire at 68 F (20 C), computed based on 100% IACS conductivityReview note: Capture never says annealed; note [7] gives solid copper at 68 F (20 C) and 100% IACS, so the temperature condition is lost. | claim | en.wikipedia.org 2026-11-09“18 0.0403 1.024 24.8 9.77 1.62 0.823 20.95 6.385 10 14 16” |