| Current rating | 1.4 A stated as ampacity | NASA EEE-INST-002 Table 4A derated current, bundled wire or multi-conductor cable; ambient 70 C or less, hard vacuum 1E-6 torr, 200 C rated wire such as PTFE; use 80 percent for 150 C wire and 70 percent for 135 C wire | spec | nepp.nasa.gov 2026-11-08“26 2.5 1.4” |
|---|
| 2.5 A stated as ampacity | NASA EEE-INST-002 Table 4A derated current, single wire; ambient 70 C or less, hard vacuum 1E-6 torr, 200 C rated wire such as PTFE; use 80 percent for 150 C wire and 70 percent for 135 C wire | spec | nepp.nasa.gov 2026-11-08“26 2.5 1.4” |
| 2.2 A stated as ampacity | PowerStream guideline, maximum amps for chassis wiring, meant for wiring in air and not in a bundle; the site calls it a rule of thumb | claim | powerstream.com 2026-11-09“26 0.0159 0.40386 0.128 40.81 133.8568 2.2 0.361” |
| 0.361 A stated as ampacity | PowerStream guideline, maximum amps for power transmission, uses 700 circular mils per amp, which the site calls very conservative | claim | powerstream.com 2026-11-09“26 0.0159 0.40386 0.128 40.81 133.8568 2.2 0.361” |
| 1.3 A stated as ampacity | Wikipedia AWG table, 60 C insulation column; enclosed wire at 30 C ambient, or single unbundled wires in equipment for 16 AWG and thinner | claim | en.wikipedia.org 2026-11-09“26 0.0159 0.405 62.7 24.7 0.254 0.129 133.9 40.81 1.3 2.2 —” |
| 2.2 A stated as ampacity | Wikipedia AWG table, 75 C insulation column; enclosed wire at 30 C ambient, or single unbundled wires in equipment for 16 AWG and thinner | claim | en.wikipedia.org 2026-11-09“26 0.0159 0.405 62.7 24.7 0.254 0.129 133.9 40.81 1.3 2.2 —” |
| Conductor area | 253 circular mils = 0.1282 mm² | NIST Handbook 100 Table 5, standard annealed copper, solid round AWG size; a stranded wire's area differs | spec | nvlpubs.nist.gov 2026-11-09“26 15.9 253 .000 199 41.0” |
|---|
| 0.129 mm2 | Wikipedia AWG table, solid round conductor | claim | en.wikipedia.org 2026-11-09“26 0.0159 0.405 62.7 24.7 0.254 0.129 133.9 40.81 1.3 2.2 —” |
| Resistance per length | 41.0 ohms per 1,000 feet | NIST Handbook 100 Table 5, standard annealed copper at 20 C, solid round AWG size | spec | nvlpubs.nist.gov 2026-11-09“26 15.9 253 .000 199 41.0” |
|---|
| 133.9 mOhm/m | Wikipedia AWG table, solid copper wire at 20 C, 100% IACS conductivityReview note: Temperature and solid-wire basis are lost: the table's footnote 7 says solid copper at 20 C and 100% IACS; the word annealed is not in the capture. | claim | en.wikipedia.org 2026-11-09“26 0.0159 0.405 62.7 24.7 0.254 0.129 133.9 40.81 1.3 2.2 —” |